SKU #: GDN1046 | Part #: QT15068C

Generac 150 kW Generac Liquid-Cooled Generator, CSA, SCAQMD, EPA Compliant in Aluminum - QT15068C

(View all from Generac)


Changing Image...
Generac 150 kW Generac Liquid-Cooled Generator, CSA, SCAQMD, EPA Compliant in Aluminum

$28,938.00 (Varies with options)
List Price: $55,515.12
You Save:

$26,577.12 (48%) 
REWARDS ?
Earn $868.14

Free Shipping!
Like what you see? Configure this item below.Or click here to view more product info.

Choose From:
150 kW Guardian Elite Commercial Series Liquid Cooled Automatic Standby Generator
150 kW Guardian Elite Commercial Series Liquid Cooled Automatic Standby Generator
stock status unknown 

Included 
Make it Yours:
Total Price:
$0.00
(0 item(s))

?When you save this item for later, you can come back to it on your shopping cart page or from the link in the store header. This item stays there until you clear your browser cookies or change your login information.

Product Details
This Aluminum generator is ideal for a broad range of enterprises, including restaurants, convenience stores, supermarkets, banks, fitness centers, hotels, and retail outlets. Keep your business "in business" and protect your revenue stream by investing in a reliable yet affordable back-up power source. One of the quietest liquid cooled generators on the market this model features the exclusive patent-pending Whisper-Test low speed generator test cycle which reduces noise by 50%. Achieves near silent operation that satisfies all known sound ordinances.

Features:

  • Aluminum Enclosure
  • Liquid cooled engine produces more electricity for longer outages
  • Whisper-Test™: Patent-pending, self-test feature makes the GUARDIAN Elite 50% quieter during the generator’s weekly self-test cycle
  • Longest life expectancy in the industry: Over 3,000 hours of run time
  • Superior Paint: Tough, textured powder coat finish for unmatched durability and all weather protection
  • UL listed
  • Clean burning fuel: Natural gas or liquid propane vapor

Generator Specifications:

  • Rated Power LPG (kW): 150
  • Rated Power NG (kW): 150
  • Amps @ 240V, 1 Phase: 625
  • Amps @ 208V, 3 Phase: 520
  • Amps @ 480V, 3 Phase: 226
  • Voltage @ 60 Hz: (120/240, 1 Phase), (120/208, 3 Phase),(120/240, 3 Phase),(277/480, 3 Phase)
  • Phase: Single and Three Phase
  • Frequency: 60 Hz
  • Engine/Alternator RPM: 3600/3600
  • Engine: 6.8L V-10
  • Fuel: Natural Gas or Liquid Propane Vapor
  • Fuel Consumption LP (cu.ft/hr)/(gal/hr): 830/22.8
  • Fuel Consumption NG (cu.ft/hr): 2061
  • EPA CARB Certified: NO
  • Engine Cooling: Liquid
  • Controls: H-100
  • UL 2200 (US and Canada): YES
  • Main Line Circuit Breaker: 700,600,250 Amp
An Automatic Transfer Switch makes the difference between a truly automatic generator set and just another generator. When the power goes out, this switch automatically senses the failure, turns on your generator, and routes electricity to the circuits of your home. No toggles to flip, no knobs to turn, no extension cords to run during a blackout. You will have the comfort and peace-of-mind knowing that your Guardian stand-by generator does everything for you...automatically!

Automatic Transfer Switch (HTS-N) Features:

  • Single coil design, electrically operated and mechanically held
  • Programmable exercise time
  • SPDT aux contacts
  • Main contacts are silver alloy
  • Conformal coating protects the printed circuit board
  • UL 1008 listed
  • Indicating LED's for switch position, standby operating, and utility available
  • 3 positions test switch: Fast test, auto, normal test
  • Arc chutes on main contacts
  • Signal before transfer contacts
  • Rated to all classes of loads
  • Remote start, stop and transfer through GenLink Communications Software

100 Amp Automatic Transfer Switch (HTS-N) Specifications:

  • Designed to operate in conjunction with the Generac H100 Series generator controller
  • 2-wire RS485 communication link to the generator controller
  • Switch operation is instigated by the generator controller
  • All timers and voltage set points are programmable through GenLink Communications Software
  • Standby Accept Voltage: 85-95%
  • Standby Accept Frequency: 85-95%
  • Nominal Voltage: 1 Volt Increments
  • Allowable Deviation of Utility: 1 - 100%
  • Line Interruption Delay: 1 - 10 seconds
  • Engine Warmup Time: 1 - 300 seconds
  • Minimum Run Time: 5 - 60 min.
  • Return to Utility Timer: 1 - 30 min.
  • Engine Cooldown Timer: 1 - 30 min.
  • Signal Before Transfer Timer: 1 - 30 sec.
  • Transfer Type: Inphase Time Delay Neutral
  • Terminal Lug Wire Contact Terminals: 2/0 - 14 AWG
  • Number of Lugs: 4
  • Maximum RMS Symmetrical Faul Current: Fuse - 200,000 Amps, Circuit Breaker - 14,000
  • Maximum Fuse Size: 200 Amps
  • Fuse Class: J, T
150 Amp Automatic Transfer Switch (HTS-N) Specifications:
  • Designed to operate in conjunction with the Generac H100 Series generator controller
  • 2-wire RS485 communication link to the generator controller
  • Switch operation is instigated by the generator controller
  • All timers and voltage set points are programmable through GenLink Communications Software
  • Standby Accept Voltage: 85-95%
  • Standby Accept Frequency: 85-95%
  • Nominal Voltage: 1 Volt Increments
  • Allowable Deviation of Utility: 1 - 100%
  • Line Interruption Delay: 1 - 10 seconds
  • Engine Warmup Time: 1 - 300 seconds
  • Minimum Run Time: 5 - 60 min.
  • Return to Utility Timer: 1 - 30 min.
  • Engine Cooldown Timer: 1 - 30 min.
  • Signal Before Transfer Timer: 1 - 30 sec.
  • Transfer Type: Inphase Time Delay Neutral
  • Terminal Lug Wire Contact Terminals: 400MCM - 4 AWG
  • Number of Lugs: 4
  • Maximum RMS Symmetrical Faul Current: Fuse - 200,000 Amps, Circuit Breaker - 25,000
  • Maximum Fuse Size: 400 Amps
  • Fuse Class: J, T
200 Amp Automatic Transfer Switch (HTS-N) Specifications:
  • Designed to operate in conjunction with the Generac H100 Series generator controller
  • 2-wire RS485 communication link to the generator controller
  • Switch operation is instigated by the generator controller
  • All timers and voltage set points are programmable through GenLink Communications Software
  • Standby Accept Voltage: 85-95%
  • Standby Accept Frequency: 85-95%
  • Nominal Voltage: 1 Volt Increments
  • Allowable Deviation of Utility: 1 - 100%
  • Line Interruption Delay: 1 - 10 seconds
  • Engine Warmup Time: 1 - 300 seconds
  • Minimum Run Time: 5 - 60 min.
  • Return to Utility Timer: 1 - 30 min.
  • Engine Cooldown Timer: 1 - 30 min.
  • Signal Before Transfer Timer: 1 - 30 sec.
  • Transfer Type: Inphase Time Delay Neutral
  • Terminal Lug Wire Contact Terminals: 400MCM - 4 AWG
  • Number of Lugs: 4
  • Maximum RMS Symmetrical Faul Current: Fuse - 200,000 Amps, Circuit Breaker - 25,000
  • Maximum Fuse Size: 400 Amps
  • Fuse Class: J, T
300 Amp Automatic Transfer Switch (HTS-N) Specifications:
  • Designed to operate in conjunction with the Generac H100 Series generator controller
  • 2-wire RS485 communication link to the generator controller
  • Switch operation is instigated by the generator controller
  • All timers and voltage set points are programmable through GenLink Communications Software
  • Standby Accept Voltage: 85-95%
  • Standby Accept Frequency: 85-95%
  • Nominal Voltage: 1 Volt Increments
  • Allowable Deviation of Utility: 1 - 100%
  • Line Interruption Delay: 1 - 10 seconds
  • Engine Warmup Time: 1 - 300 seconds
  • Minimum Run Time: 5 - 60 min.
  • Return to Utility Timer: 1 - 30 min.
  • Engine Cooldown Timer: 1 - 30 min.
  • Signal Before Transfer Timer: 1 - 30 sec.
  • Transfer Type: Inphase Time Delay Neurtal
  • Terminal Lug Wire Contact Terminals: 600MCM - 4 AWG or (2)250MCM-1/0 AWG
  • Number of Lugs: 4
  • Maximum RMS Symmetrical Faul Current: Fuse - 200,000 Amps, Circuit Breaker - 35,000
  • Maximum Fuse Size: 600 Amps
  • Fuse Class: J, T
400 Amp Automatic Transfer Switch (HTS-N) Specifications:
  • Designed to operate in conjunction with the Generac H100 Series generator controller
  • 2-wire RS485 communication link to the generator controller
  • Switch operation is instigated by the generator controller
  • All timers and voltage set points are programmable through GenLink Communications Software
  • Standby Accept Voltage: 85-95%
  • Standby Accept Frequency: 85-95%
  • Nominal Voltage: 1 Volt Increments
  • Allowable Deviation of Utility: 1 - 100%
  • Line Interruption Delay: 1 - 10 seconds
  • Engine Warmup Time: 1 - 300 seconds
  • Minimum Run Time: 5 - 60 min.
  • Return to Utility Timer: 1 - 30 min.
  • Engine Cooldown Timer: 1 - 30 min.
  • Signal Before Transfer Timer: 1 - 30 sec.
  • Transfer Type: Inphase Time Delay Neurtal
  • Terminal Lug Wire Contact Terminals: 600MCM - 4 AWG or (2)250MCM-1/0

    See something odd? Report it here.

Additional Info

Weight & Dimensions

See below

Shipping Info

Free Shipping!
Ships to:    
Ships via Truck Freight Delivery (Learn More)
Weight, Dimensions & Additional Features
Item: Dimensions: Weight:
150 kW Guardian Elite Commercial Series Liquid Cooled Automatic Standby Generator54.8" H x 36.8" W x 115.2" D2666 lbs

Additional Features
Application:Commercial Standby Generators
Available Transfer Switch:Yes
Dual Fuel:Yes
Emissions Certifications Options:California Air Resource Board Compliant, Canadian Standards Association
Enclosure:Steel Enclosure
Engine Speed:1800 Rpm
Epa/Carb Certified:No
Load Management System:No
Operation:Automatic Standby Generators
Phase Options:Single Phase Standby Generators, Three Phase Standby Generators
Power Source Options:Liquid Propane Standby Generators, Natural Gas Standby Generators
Product Category:Standby Generators
Rated Voltage Options:208 Volt, 240 Volt, 480 Volt
Rated Wattage:70 - 150 Kilowatts
Reduced Noise:Yes
Standby Generator Output:Whole House
Towable:No
Voltage Regulator (Computer Friendly):No

back to top

Questions & Answers
Have a question? We want to know   

We're sorry, we have no FAQs to display. 
back to top

Reviews

See Similar Products
▪ View more products from: Generac
▪ View more: Standby Generators
Related Products
Steel enclosure. Convenient, hands free operation no fueling, ...
The NEW Steel Guardian 17 kW standby generator ...
The NEW Guardian 14 kW standby generator provides ...
Reference
OUR SKU # GDN1046 This item is also sometimes listed under the following manufacturer numbers: HTSN100A1, HTSN100A3, HTSN100G1, HTSN100G3, HTSN100K1, HTSN100K3, HTSN150A1, HTSN150A3, HTSN150G1, HTSN150G3, HTSN150K1, HTSN150K3, HTSN200A1, HTSN200A3, HTSN200G1, HTSN200G3, HTSN200K1, HTSN200K3, HTSN300A1, HTSN300A3, HTSN300G1, HTSN300G3, HTSN300J1, HTSN300J3, HTSN300K1, HTSN300K3, HTSN400A1, HTSN400A3, HTSN400G1, HTSN400G3, HTSN400J1, HTSN400J3, HTSN400K1, HTSN400K3, HTSN600A3, HTSN600A4, HTSN600G3, HTSN600G4, HTSN600K3, HTSN600K4, HTSN800A3, HTSN800A4, HTSN800G3, HTSN800G4, HTSN800K3, HTSN800K4, QT13068C, QT15068C

back to top

ServerT:0.34941983222961